1.1. This explosion proof HVAC is used for process analyzer shelters, analyzer houses,it can provide positive pressure air into the shelter, so it is also called explosion proof positive air conditioner.This explosion proof air conditioning system can keep the room’s air pressure higher than the outside air ,this can stop the outside dangerous air entering into the room,keeping the workers safe in inside the room.
1.2. This type explosion prof HVAC units are designed to provide cooling, heating, pressurization, fresh air purging in one assembly. They are typically furnished for instrument control room, laboratory, measuring room, analyzer shelter etc in hazardous locations.

1.3. Case material:Carbon steel with corrosion-proof painting, Stainless steel (304 or 316).
1.4. Customized alarm or control functions intend for meet control of analyzer shelter

1.5. Copper tube copper finned coils, corrosion protection coating coils,Stream heating coils
1.6. Full redundant heating, ventilation, air conditioning combined into single package is available
1.7. Remote control interface is available.
1.8. Medium efficiency particulate air filter, HEPA filter..

1.9 This type of explosion proof HVAC is up to the standards of the products quality surveillance of national explosion-proof electrification, and has obtained the explosion proof certificate . Such explosion proof split wall mount air conditioners can be used in Used in the hazard area:

 Zone 1,Zone 2 ,Groups IIA,IIB,IIC (IEC hazard area classification),

Class 1/Division 1,Class 1/Division 2, Group B,C,D area.(NEC hazard area classification).

Category 2G,3G(ATEX hazard area classification)

Suitable used in the temperature range:T1,T2,T3,T4

Explosion-proof mark : Exdmbib Ⅱ BT4, Exdmbia Ⅱ CT4  .Explosion proof protection can be designed according to the ambient environment.

This explosion Proof air conditioning and air ventilating system is produced based on the explosion proof equipment standards as below:

GB3836.1-2010《Electrical apparatus for explosive gas atmospheres Part one: General requirements and test methods》, which is equivalent to IEC60079-0:2007

GB3836.2-2010《Electrical apparatus for explosive gas atmospheres Part two: Flameproof enclosure “d”》,which is equivalent to IEC 60079-1:2007

GB3836.4-2010《Electrical apparatus for explosive gas atmospheres Part four: Intrinsic safety “i”》,which is equivalent to IEC 60079-11:2006)

GB3836.9-2006 《Electrical apparatus for explosive gas atmospheres Part nine: Encapsulation “m”》,which is equivalent to IEC 60079-18:2004 .

GB/T17758-2010 《unit type explosion proof air conditioner》

Type/Tech.data

BST-8P

BST-10P

BST-12P

BST-16P

BST-24P

Cooling Capacity(kW)

8

10

12

16

24

Electric Heating Capacity(kW)

6

8

8

8

8

Cool   air flow(m3/h)

1450

2340

3000

3670

5260

Full pressure(Pa)

400

420

420

450

500

Total power(kW)

8.22

14.9

11

11.9

16.9

Over pressure   (Pa)

25~250(adjustable)

Power supply

380V/415V/460V  50/60Hz    3 Phase

Evaporator

Air  Fan

Quantity

1+1

Power

(kW)

0.4+0.4

0.45+0.45

0.55+0.55

0.75+0.75

1.1+1.1

Condenser

Air Fan

Quantity

2

2

2

2

2

Power

(kW)

0.3

0.75

0.9

1.2

2.2

Refrigerant

Type

R22

Weight kg

3.5

4.5

5

5.8

7.8

Compressor

Quantity

1

1

1

1

1

Power

(kW)

3.5

4

4.6

5

8

Fresh   air intake m3/h

300

345

500

648

1080

Control   temp.range ℃

15~28

Size

L(mm)

1500

1500

1500

1600

1800

W(mm)

1000

1000

1000

1200

1500

H(mm)

2000

2170

2170

2400

2600

Ex Marking

Ex  d ib mb    ⅡC  T4  Gb